6ES7316-2AG00-0AB0
CPU316-2DP, 128KB

From SIEMENS

***Spare part*** SIMATIC S7-300, CPU 316-2DP Central processing unit with integr. Power supply 24 V DC, Work memory 128 KB 2nd interface DP master/slave
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption (rated value)1 000 mA
Inrush current, typ.8 A
Power loss
Power loss, typ.10 W
Memory
Work memory
integrated128 kbyte; 128 KB / 42K instructions RAM (integrated)
Load memory
expandable FEPROMYes; Flash-EPROM
expandable FEPROM, max.4 Mbyte
integrated RAM, max.192 kbyte
Backup
presentYes
with batteryYes; all blocks
without batteryYes; 4 KB: bit memory, counter, times and data
CPU processing times
for bit operations, typ.0.3 µs
for bit operations, max.0.6 µs
for word operations, typ.1 µs
for fixed point arithmetic, typ.2 µs
for floating point arithmetic, typ.50 µs
for timer/counter operations, typ.12 µs
CPU-blocks
DB
Number, max.511
Size, max.16 kbyte
FB
Number, max.256
Size, max.16 kbyte
FC
Number, max.256
Size, max.16 kbyte
OB
Descriptionsee instruction list
Size, max.16 kbyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of cyclic interrupt OBs1; OB 35
Number of process alarm OBs1; OB 40
Number of startup OBs1; OB 100
Nesting depth
per priority class8
Counters, timers and their retentivity
S7 counter
Number64
Retentivity
— adjustableYes
— lower limit0
— upper limit63
Counting range
— lower limit1
— upper limit999
S7 times
Number128
Retentivity
— adjustableYes
— lower limit0
— upper limit127
Time range
— lower limit10 ms
— upper limit9 990 s
Data areas and their retentivity
Flag
Number, max.256 byte
Retentivity availableYes; MB 0 to MB 255
of which retentive with battery0 to 2 047 (M 0.0 to M 255.7, adjustable)
of which retentive without battery0 to 2 047 (M 0.0 to M 255.7, adjustable)
Address area
I/O address area
Inputs2 kbyte
Outputs2 kbyte
Process image
Inputs128 byte
Outputs128 byte
Digital channels
Inputs16 384
— of which central1 024
Outputs16 384
— of which central1 024
Analog channels
Inputs1 024
— of which central256
Outputs1 024
— of which central128
Hardware configuration
Number of expansion units, max.3
connectable programming devices/PCsPGs/PCs with STEP 7 connectable via MPI interface
Number of modules per DP slave interface, max.64
Number of DP masters
integrated1
via CP1; CP 342-5
Number of operable FMs and CPs (recommended)
FM8
CP, PtP4
CP, LAN2
Rack
Modules per rack, max.32
Time of day
Clock
Hardware clock (real-time)Yes
Interfaces
MPI
Cable length, max.9 100 m; without repeaters: 50 m; with 2 repeaters: 1100 m; with 10 repeaters in series: 9100 m; via fiber optic cable: 23.8 km (with 16 star hubs or OLMs)
1. Interface
Protocols
MPIYes
MPI
Number of nodes, max.32
Transmission rate, min.19.2 kbit/s
Transmission rate, max.187.5 kbit/s
Services
— PG/OP communicationYes
— Global data communicationYes
— S7 basic communicationYes
— S7 communicationYes
2. Interface
Protocols
PROFIBUS DP masterYes
PROFIBUS DP slaveYes
PROFIBUS DP master
Number of DP slaves, max.124
Services
— EquidistanceYes
— Activation/deactivation of DP slavesYes
— Direct data exchange (slave-to-slave communication)Yes; Transmitter and receiver
User data per DP slave
— User data per DP slave, max.244 byte
Communication functions
PG/OP communicationYes
Global data communication
supportedYes
S7 basic communication
supportedYes
S7 communication
supportedYes
as serverYes
S5 compatible communication
supportedYes; via loadable blocks
Standard communication (FMS)
supportedYes; via loadable blocks
Number of connections
overall
— of which dynamic8
— of which static4
Configuration
Configuration software
STEP 7Yes; V5.0
Programming
Command setBinary logic operations, bracketed operations, result allocation, saving, counting, loading, transferring, comparing, shifting, rotating, complementation, calling blocks, fixed point arithmetic, floating point arithmetic, jump functions
Nesting levels8
Program organizationLinear, structured
System functions (SFC)Interrupt and error processing, copy data, clock functions, diagnostic functions, module parameterization, operating mode transitions
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— CFCYes
— GRAPHYes
— HiGraph®Yes
Software libraries
— Process diagnosticsYes
— Software controllerYes; depending on the required memory space and the resulting execution time
Know-how protection
User program protection/password protectionYes
Cycle time monitoring
lower limit1 ms
upper limit6 000 ms
adjustableYes
preset150 ms
Dimensions
Width80 mm
Height125 mm
Depth130 mm
Weights
Weight, approx.530 g; Memory card 16 g
last modified:03/13/2019